MCII Tempatrol Instructions

MCII®  
TEMPATROL® INSTRUCTION

POWER UP DIAGNOSTICS STAGE 2
DISPLAY FUNCTIONS DIAGNOSTICS STAGE 3
MCII PROGRAMMING CONTROL MODULE
DIAGNOSTICS (BASIC) POWER MODULE CONNECTOR
SIMPLE SYSTEMS CHASER VOLTAGE TABLE

  POWER UP

The Delfield 6000 series and Spec Line Refrigerators and Freezers with the MCII Tempatrol (microprocessing unit) will operate immediately upon start-up without any programming.  The freezer temperature is preset from the factory to 0° F and the refrigerator is preset to 37°F.

When the unit is started, the digital display will flash if over temp (32° F on Freezers, 65º F on refrigerators).  This is a signal that the unit has been Powered up or that there has been a loss of power.  Every time the unit is started or restarted, the time of day must be set.

Pressing the RESET displays the box temperature.  The temperature will remain flashing if the box is over temp.  Flashing will stop when the over-temp condition is gone.

Instructions for setting the time and other programming follow a description of the Display Functions.

 

 

  DISPLAY FUNCTIONS

Normal Display is the box temperature in degrees Fahrenheit.  Pressing the RESET button will always bring up the box temperature display.  By pressing TEMP, you can read the set point of the box.  The display will automatically return to the box temperature after one minute of displaying alternate information.

It is not unusual for the box temperature to rise rapidly when doors are opened.  The temperature displayed is usually the warmest temperature inside the box.  This is done purposely to make sure that the entire storage area is always represented by the display and assures that the refrigeration system is activated quickly to return the storage area to its correct temperature.

Remember the temperature displayed represents a precision measurement of the actual air temperature, not the average temperature.  When a door is opened the cold air literally falls out and warm air rushes in.  What the display shows is real and will provide more accurate control.

Flashing Temperature Display can be caused by four situations and is the first signal of a possible problem.

  1. Unit has not reached the set temperature
  2. The box is over temperature.  This occurs when a freezer reaches 32°F or a refrigerator reaches 65°F.  This condition will stop when the temperature falls below 32°F (freezer) or 65°F (refrigerator).
  3. Long duty cycle.  The unit has been running for one continuous hour without the doors being opened.  This condition will stop if RESET is pressed, the door is opened or the compressor shuts off.
  4. The door has been ajar for one minute.  This condition will stop if the door is closed.

 Door Ajar Light will come on when the door is open.  After one minute the temperature display will flash.  After three minutes a loud beep every three seconds is emitted.  The display and beeper will stop when RESET is pressed.  If the door is not closed when RESET is pressed the same cycle will repeat.

Clean Condenser.  This maintenance reminder comes on every 90 days and will go off when RESET is pressed.

Defrost. This indicator light comes on during defrost.  Defrost can be terminated if RESET is pressed.  Warmer box temperatures are expected during and after defrost.

Check System indicates a significant malfunction, such as an incomplete defrost, continuous compressor operation with continuous over-temp condition or sensor failure.  After 2½ hours in this condition a loud beep is emitted every second.  The beeper will stop if RESET is pressed.

Time of Day.  The correct time is not essential to operation, but is necessary for correct defrost timing when not in Automatic (A) mode.  The time will have to be reset whenever power is interrupted for correct defrost timing.

Custom Defrost – Freezers Only  A four times per day defrost cycle is preset at the factory, however, a custom defrost cycle can be set.  The last defrost program is always kept in memory even in power is lost.  Correct time of day is essential if a custom defrost cycle is set.

When programming the custom defrost cycle, the display will offer a choice of “A” or 3, 4, 6 or 8.

To set the custom defrost cycle you first determine when defrosts are desired or not desired and estimate the number of defrosts required.

3 a day = Light duty (1 door opening per hour)
4 a day = Normal usage (3 door openings per hour)
6 a day = High usage (4 or more door openings per hour)
8 a day = Very high usage (more than 8 door openings per hour)

Defrosts will occur at regular intervals, according to settings:
3 = One defrost every 8 hours
4 = One defrost every 6 hours
6 = One defrost every 4 hours
8 = One defrost ever 3 hours 

Based on your selection enter a time for the first defrost so that it and all subsequent defrosts occur at suitable times.  Also, more defrosts should be added in a high humidity environment.

For example, in Maxfield’s Café defrost cycles were not wanted during peak times of 7:00 a.m., noon, and 5:00 p.m.  The freezer is used heavily during these periods but the rest of the day is normal duty; the humidity in the café is also high.  Therefore, we estimate that four defrosts are required per day and they will occur every six hours.

To avoid 7:00 a.m. rush we set the first defrost at 8:00 a.m.  Subsequent defrosts occur at 2:00 p.m., 8:00 p.m. and 2:00 a.m. neatly missing the defined rush periods.

We recommend that the first defrost be set to follow heaviest usage.

Automatic or  Demand Defrost.  If the Automatic (A) defrost is selected the MCII will monitor usage and efficiency of the unit, and will defrost automatically only when needed.  This setting is highly recommended for very light duty and basic storage applications.  It is also recommended for all applications when the time of the defrost is not important.  In the Automatic mode it is possible for the unit to operate for several days without defrosting.

By eliminating unnecessary defrosting significant energy savings can be realized.  Fewer defrosts also lead to a more constant temperature control and longer product life.

Manual Defrost.  A defrost can be initiated at any time by pressing DEFROST and TIME simultaneously.  The defrost can be terminated by pressing RESET.

  MCII PROGRAMMING

Setting Time of Day

  1. Press RESET to insure you are at a normal operating display.
  2. Press TIME to show current time (the last time the unit was shut down or lost power will be displayed).
  3. Press UP or DOWN to set correct time.  Note: AM and PM indicators at left of display.
  4. Press TIME or RESET to return to box temperature display.

 Setting Defrost Cycles (Freezer Only) A defrost cycle is pre-programmed at the factory and no adjustment is necessary to use the unit.  A custom defrost cycle or automatic/on demand cycle can be programmed if desired.  To change defrost cycle or set new cycle:

  1. Press DEFROST “A, 3, 4, 6 or 8” will be displayed .  A = Automatic/demand defrost.  3, 4, 6 or 8 = number of defrosts per a 24 hour period.
  2. Press UP or DOWN to desire selection.
  3. Press DEFROST again: If you selected A it will return to temperature display, if you selected 3, 4, 6 or 8 time of first defrost is displayed.
  4. Press UP or DOWN to set hour of first defrost.  Other defrosts will be spaced evenly over the following 24 hour period.  See Basic Operation section on how to select specific defrost times.
  5. Press DEFROST or RESET to return display to box temperature.

 Setting box temperature. Box temperatures are programmed at the factory at 0°F for the freezer and 37° for the refrigerator.  The recommended storage temperature range is –5° to 0°F for the freezer and 35° to 40° F for the refrigerator.  If other ranges are selected they must be suitable for all products being stored.

  1. Press RESET to display box temperature.
  2. Press TEMP to display current set point.
  3. Press UP and DOWN to select desired set point.  The refrigerator can be set from 34° to 45°F (35° to 40° F recommended) and the freezer can be set from –5° to 10ºF (–5° to 0°F recommended).
  4. Press RESET or TEMP to return to box temperature display.

  DIAGNOSTICS - STAGE 1 (BASIC)

INDICATION

CAUSE

WHAT TO DO

THINGS TO CHECK
Flashing temp display above 32º on freezer above 65º on refrigeratorOver TempKeep doors closed
Let unit pull down
Watch and wait
Was unit just turned on?
Is box overloaded with warm product?
Is evaporator coil clear?
Is there, or has there been a CHECK SYSTEM indication?
Did unit just defrost?
Flashing temp display below 32º on freezer below 65º on refrigeratorLong Duty CyclePress RESET
Let unit pull down
Watch and wait
Was box recently loaded with warm product?
Is room temperature high?
Does display flash again after one hour?
Flashing display returns after one hourContinuous compressor operationPress RESET
Let unit pull down
Watch and wait
Is set point too low?
Is condenser clean?
Is box heavily loaded?
Is evaporator clear?
Is room temperature high?
Door ajarDoor OpenClose doorIs something blocking the door?
Door ajar with flashing temp display, and three second beepDoor open after 1minute
Door open after 3 minutes
Press RESET for temporary clear if door is being kept open intentionallyIs door being held open longer than needed?
Clean condenser90 day timerClean condenser
Press RESET
Have all maintenance procedures been performed on unit?
DefrostIn defrost  
Check system with flashing temp displayOver temp for 1 hour with doors kept closedCheck diagnostic code number (see Stage 2 diagnostics)Is box overloaded with warm product?
Is the evaporator clear?
Is the condenser clean?
Check system without flashing temp displayIncomplete defrost or some other problem detected by the controlCheck diagnostic code number (see Stage 2 diagnostics)Call a qualified service agent.
Check system with flashing temp and alarmOver temp for 2½ hours with doors kept closedCheck diagnostic code number (see Stage 2 diagnostics)Call a qualified service agent.
Check system with alarm and 33 degree displaySensor failureTry pressing RESET
Call for service if alarm cannot be cleared
Check sensor wiring for broken or loose wire.

Note: Repeated problem of flashing display indicates very high compressor activity, make sure routine maintenance procedures are performed regularly.

Note: Whenever a check system indication appears, a potentially serious problem has occurred.  Appropriate action should be taken immediately to insure proper product temperature.

Note: A check system and all warnings can be temporarily cleared by pressing RESET, however pressing reset will not normally correct a system problem


 

 SIMPLE SYSTEM CHECKS

ITEM

METHOD OF CHECKING

NORMAL INDICATION

Time of dayPress TIMECorrect time of day.
Defrost settings (freezers only)Press DEFROST
Press DEFROST twice
A or 3 or 4 (may also be a 1 or 2 or 6)
Time of first defrost cycle (if in A mode, should return to temperature display.
Set point (temperature setting)Press TEMPRefrigerator - 35º to 40º F
Freezer - 5º to 0ºF
(may be 34º to 45º on refrigerator, 5º to 10º on freezer)
Present box tempPress RESETWithin 2 degrees of set point
Evaporator tempPress RESET then DOWN (during normal operation) compressor runningFreezer = -20º to 0ºF (up to 55º during defrost)
Refrigerator =10º to 40ºF
Evaporator temp #2 (freezers only)Press RESET then UP (during normal operation) compressor runningFreezer = -20º to 0ºF
Refrigerator =-33ºF (no sensor)

  DIAGNOSTICS – STAGE 2

System checks in case of CHECK SYSTEM indication

A. Enter Diagnostic Mode

  1. Press DOWN and TIME together, then press TEMP

  2. Diagnostic Code should appear.

  3. Code numbers indicate problem area to check:

000 = no problem

001 = check refrigerant

002 = check evaporator and/or air flow

003 = check compressor

004 = check entire system

005 = check defrost

006 = check box sensor –33

007 = check control system (memory failure)

  1. Designed to aid service technician

  2. Refer to trouble shooting chart for additional help.

B. Leave Diagnostics

  1. Press RESET.

  2. CHECK SYSTEM indicator will go off unless box sensor problem.

  3. CHECK SYSTEM will re-appear in one hour if an over temp condition still exists.

  DIAGNOSTICS – STAGE 3

Relay operation check and factory programming codes

A. Enter Diagnostic Mode (Stage 2)

  1. Press DOWN and TIME together, then press TEMP

  2. Diagnostic code number should appear.

B. Enter Diagnostics - Stage 3

  1. Press DEFROST.

  2. Service check code number of 000 should appear.

  3. Press UP/DOWN to obtain desired service check function:

000 = temp scale (ºF or ºC)

001 = check fan relay for one minute

002 = check compressor relay for one minute

003 = check light relay for one minute

004 = check defrost relay for one minute

005 = factory programming code

006 = factory programming code

007 = factory programming code

008 = clear error codes

009 = lock out option

010 = alarm options

011 = power up options

012 = select basic function

013 = temperature setpoint differential options

014 = fan relay function (freezer only)

015 = temperature range

016 = check vfd display

 

  1. Press TIME to initiate the checking action

  2. Energized relay will stay on for one minute or until next service check is initiated

  3. Press RESET at any time to exit diagnostic mode

 C. Leave Diagnostics

  1. Press RESET

  2. CHECK SYSTEM indicator should go off

  3. Normal box temperature display should return

Factory Programming Defrost Adjustments

Service Check Code

005

006

007

Defrost Function

Termination time limit

Termination time limit

Fan delay cut-in temp

Function Code Number

Degrees F

Minutes

Degrees F

0:01
0:02
0:03
0:04
0:05
0:06
0:07
0:08
0:09

NONE
40
45
50
55
60
65
70
75

NONE
15
20
25
30
40
45
60
90

NONE
10
20
25
30
35
40
50
60

 

 

A. ENTER DIAGNOSTIC MODE – STAGE 3

 

  1. Press DOWN and TIME together, then TEMP (Diagnostic Entry)

  2. Press DEFROST (Enter stage 3)

  3. Press UP/DOWN until correct service code appears (See chart above)

  4. Press TIME and HOLD


     

    1. Factory function code number appears

    2. Press UP/DOWN to change code (see chart)

  5. Each service code (005, 006, and 007) is normally as indicated in above chart

  6. Each service code may be set with a different function code number

EXAMPLE:
Factory defrost settings are:

  1.  
    1. Termination temp (Service Code 005) = 55°F (Function code No. 0:05)

    2. Time limit (Service Code 006) = 45 minutes (Function code No. 0:07)

    3. Fan cut-in (Service Code 007) = 30º F (Function code  No. 0:05)

Want Defrost Settings:

A.    Termination temp (Service Code 005) = 70ºF (Function code No. 0:08)

B.     Time limit (Service Code 006) = 30 minutes (Function code No. 0:05)

C.    Fan cut-in (Service Code 007) = NONE (Function code  No. 0:01)

B. Leave Diagnostics

  1. Press RESET

  2.  Normal box temperature display should return.

POWER MODULE

Voltage Readings

9 and 10 – 2.8 VAC for heating up vacuum florescent yellow to yellow from transformer

7 and 1 – 35 VDC for defrost relay
7 and 2 – 35 VDC for compressor relay
7 and 3 - 35 VDC for fan relay
7 and 4 – 35 VDC for light relay

Transformer readings

Yellow to yellow              2.8 VAC
Red to red                       25 VAC
Red to blue                      13 VAC

  CONTROL MODULE

Sensor
Pin connection on control module

9 and 10
Goes to jamb switch (rocker switch).  Jumping (closing the gate) these two pin terminal causes relay for light to become energized by causing a connection (gate to close) between pin terminals 7 and 4 on power module.  It also causes relay for fans to become  de-energized by breaking the connection (opening the gate) between pin terminals 7 and 3 on power modules.

7 and 8
No function.

5 and 6
Outlet sensor connection (white band).  A change in resistance (measured in OHMS) causes display to register a value corresponding to degree Fahrenheit.  The resistance to temperature values are in the LCI manual.  This temperature will be displayed while depressing the DOWN button on the control module.

3 and 4
Inlet sensor connection (red band).  A change in resistance (measured in OHMS) causes display to register a value corresponding to degree Fahrenheit.  The resistance to temperature values are in the LCI manual.  This temperature will be displayed while depressing the UP button on the control module (freezer models only, not used on refrigerators).

1 and 2
Cabinet sensor connection (green band).  A change in resistance (measured in OHMS) chases display to register a value corresponding to degrees Fahrenheit.  The resistance to temperature values are in the LCI manual.  This temperature will be displayed normally.

  DELFIELD POWER MODULE CONNECTOR CHECK OUT

Pins 9 and 10 supply the VFD with the necessary AC voltage for operation.  The voltages across these two pins can be checked using an AC voltmeter set on the 20 volt range.

Connect one lead of the meter to pin 9 and the other lead to pin 10.  A voltage reading of about 2.5V should be obtained.

Pin 8 is the high DC voltage for the VFD and relay coils.  The voltage can be checked by using a DC voltmeter on the 200 volt range.

Connect the common or ground lead of the meter to pin 7.  This is the ground signal between power and control modules.   Connect the second lead to pin 8.  A reading of 30 to 32 bolts should be obtained.  The actual voltage depends on the number of relays that are activated when the reading is taken. 

 

 

Pin 6 provides a 60 hz. Signal for time keeping purposes.  The voltages can be checked by using an AC voltmeter on the 20 volt range.

Connect one lead to pin 7 and connect the second lead to pin 6.  A reading of about 12 volts AC should be obtained.

Pin 5 provides the low DC voltage for the regulator and the horn.  It can be checked by using a DC voltmeter on the 20 volt range.

Connect the common or ground lead of the meter to pin 7.  Connect the second lead to pin 5.  A reading of 14 to 15 volts should be obtained.  The actual voltage depends on the number of relays that are activated when the reading is taken.

Pins 1 through 4 are the power line for the relay coils.  The voltage on these pins can best be checked by entering Stage 2 diagnostics and operating the relays individually.

To enter stage 2 diagnostics, press the TIME and DOWN buttons simultaneously, then within 3 seconds, press the TEMP button.  This puts the unit into stage 1 diagnostics.  Press the DEFROST button.  A number one should be displayed on the VFD.  This is stage 2 and all relays should be off at this time.

 

 

Using a DC voltmeter, the voltages on pins 1 through 4 cannot be checked.  Connect the common or ground lead of the voltage is to be checked.  The voltages for pins 1 through 4 are listed in a table.  The voltages vary depending on which relay is turned on.

With the one showing on the VFD, press the TIME button.  This activates the light relay.  Check the voltages on each of the pins 1 through 4 and compare them to the table.

Continue this procedure for number 3, the compressor relay and number 4, the defrost relay.  Pressing RESET will exit diagnostics and return to normal operating mode. 

 

 

  VOLTAGE TABLE
FOR PINS 1 THROUGH 4

ConditionFRZREFFRZREFFRZREFFRZREF
No relay on31.3N/A31531.531.5N/A31.531.5
Fans relay on 130.4N/A30.531.531.5.812.231.5
Compressor relay on 212N/A.8.830.3N/A30.530.5
Light relay on 330.4N/A30.530.511.8N/A.8.8
Defrost relay on 4.8N/A11.731.530.3N/A30.530.5

All values are DC volts
N/A = Not Applicable
REF = Refrigerator
FRZ = Freezer

The voltages given here are not exact.  Line voltage fluctuations and the normal tolerances range of various components will cause the voltages to vary.

NOTE: Whenever the control module is to be disconnected, disconnect the AC power cord from the AC service.